Phone: 801.785.4123
Fax: 801.785.6999
333 South 520 West
Lindon, UT 84042


Login
  
 
Q-TC™ Series
Traffic Controller


 

Q-TC 1000
(1000 VA / 700 Watts)
Q-TC 1500
(1500 VA / 1050 Watts)
Q-TC 2000
(2000 VA / 1400 VA)
Q-TC 3000
(3000 VA / 2000 Watts)


Series Description

The Power Innovations Q-Series™ Traffic Controller Uninterruptible Power Quality™ (UPQ™) system has been designed to condition input power and provide battery backup for traffic control systems. The Q-TC is designed for application inside a traditional semifore-type traffic controller box and suitable for operation in extreme environments, including temperature, humidity, and/or contamination. As additional protection from rust and fungus, components are treated with an anti-corrosive conformal coating prior to unit assembly.

The Q-TC is an advanced, true on-line, uninterruptible power system with outputs ranging from 1000VA to 3000VA, and suitable to accomodate virtually any traffic controller power needs. Using UPQ technology, which incorporates five (5) stages of isolation, filtration, and conversion, the Q-TC consistently produces a reliable, pure sine wave power output.

The Q-TC records and stores a cumulative count (HH:MM) of AC input power downtime. In the event of AC input failure, connected traffic signals are powered by available battery backup, thus remaining operational so long as battery power is available.

Using the Bypass Box provided with the Q-TC system, the User may manually change the source of input power. Using the Bypass Box, the User may:

  • bypass the load (traffic signal) to utility power, or
  • use an external portable/mobile source to the load (directly or via the Q-TC)

When the Bypass Box is used to divert power away from the Q-TC system, the User may remove the Q-TC module without disruption of power to the load (traffic signal) regardless of the input power source (AC utility, portable, mobile, or other).

All Q-TC models offer advanced power security through the provision of redundant features and the incorporation of an internal SNMP-Web management option (UPQnet-agent III). The UPQnet-agent III provides real-time power statistics and remote/local control of any connected system. Access to system date is available from within a network or via an Internet connection, direct dial-up, or other portable handheld device, such as a PDA and/or cell phone.

Ideally suited for:

  • Traffic Controllers

 

 
Series Features

 Complete Isolation and Protection from Input Power Problems

Q-TC Series systems are always online, and provide five (5) stages of isolation and conversion. In comparison, traditional UPS online systems provide only two (2) stages of isolation allow Q-TC Series systems to accept a wider range of input power variation (up to double that of traditional UPS systems). 

 

High Resolution Sine Wave Output

The Q-TC assures perfect power to connected equipment. The systems isolate, filter, and regulate impure and erratic input power to provide a pure and consistent sine wave output.

 

High Frequency Power Generation

High frequency generation refers to the rate and resolution by which the inverter can switch to produce a sine wave. Q-TC systems generate at 50 KHz- more than twice as fast as most traditional UPS systems. high frequency switching provides a perfect sine wave output while offering higher efficiency. Some advantages include smaller size for equal output, less weight, less heat dissipation, longer run time, and higher reliability.

 

Air Filtering

Q-TC systems incorporate negative air flow and a filtering process that together help keep vital components clean. This feature enables cooler and more reliable operation.

 

Expandable Backup Time

All battery modules are external to the standard systems. Q-TC system batteries provide five (5) minutes of backup time at full load. Backup time is expandable with additional battery modules. Cabinets are available to house and protect any configuration of battery backup modules, and may be directly connected to the system via custom Anderson Quick Disconnect Connectors (QDC) or hardwire terminal strips.

 

Advanced Protection

The Q-TC Series incorporates technologies that preserve the life of the system and connected equipment. Advanced features include:

·         Overload bypass

·         Short-circuit protection

·         Over temperature shutdown

 

Q-TC Series Features

  • Always online
  • Five (5) stages of isolation and conversion
  • Bypass load protection
  • Full feature display
  • High efficiency
  • Extended / scalable battery backup times
  • Hot-swappable batteries
  • Horizontal or vertical mounting options
  • Countdown counter
  • Auxiliary output receptacle
  • Contact closure status
  • Bypass Box (optional)
  • SNMP web management (optional)

Environmental Extremes

The Q-TC Series has been built to withstand the harshest climates and changes in the environment. Internal cooling fans are contained within the Q-TC system, allowing safe operation in conditions from -40º to 74º C. Batteries, however, can only withstand temperatures ranging from -20º to 40º C. Heat pads can be added to extend the range of low temperature tolerance for the batteries. Temperature sensors are available through the UPQnet-agent III for additional internal and external sensor points.

 

Bypass Box (optional)

Using the Bypass Box provided with the Q-TC module, the User may manually change the source of input power. Using the Bypass Box, the User may:

    1. bypass the load (traffic signal) to utility power, or

    2. use an external portable / mobile source to power the load (directly or via the Q-TC)

When the Bypass Box is used to divert power away from the Q-TC system, the User may remove the Q-TC module without disruption of power to the load (traffic signal) regardless of the input power source (AC utility, portable, mobile, or other).

 

Multiple Outputs for Traffic Controller Functions

The Q-TC Series has two AC outputs, plus an additional utility tap. One output is routed via a Bypass Box and the other is located on the back of the Q-TC system. The utility TPT (temporary power tap) is provided via a NEMA 5-15 for additional equipment connection. A terminal block is also available for direct wired connection.

 

Status Communications

The Q-TC system comes with a contact closure terminal block and an RS-232 communication port. The following contact closures are provided via the RS-232 DB-9 port: AC power failure, dual low battery, dual timer, and self-test.

 

Tri-Function Display

The Q-TC system has a tri-function LED display. The LED display shows the operating status of the system, load percentage, and the level of the battery.

 

Counter & Timer

The Q-TC records and stores a cumulative count (HH:MM) of AC input failure, connected traffic signals are powered by available battery backup, thus remaining operational so long as battery power is available.

 

UPQsoft™

UPQsoft is Power Innovations' smart UPQ local monitoring and control software for the Windows, NetWare, or UNIX/Linux environment. This software provides a real-time view of the Q-TC system status within a standalone or networked environment. Displayed in a variety of graphical and table forms, the data gives administrators access to UPQ system activity and a comprehensive history of power-related events (see UPQsoft).

 

Options to be purchased with this series:

UPQnet-agent III™

The Q-TC can be remotely monitored and managed using a UPQnet-agent III. The UPQ net-agent III provides a comprehensive, easy-to-understand, secure Web-base interface to monitor and control any UPQ system- via a network, an IP address or dial-up connection. This web page provides vital information from the Q-TC that is available both locally and remotely, and may be accessed via computer, cell phone, PDA or other electronic devices with internet connections. The UPQnet-agent III also sends TRAP and email notifications regarding system status when user-set parameters are achieved (see UPQnet-agent III).

 

 
Series Comparison

 

Q-TC 1000

Q-TC 1500

Q-TC 2000

Q-TC 3000

Output
Capacity (VA)

1000

1500

2000

3000

Capacity (Watts)

700

1050

1400

2000

Current (peak amp) 120/230 VAC

9.1 / 4.3

13.7 / 6.4

18.2 / 8.7

27.3 / 13

Waveform

High resolution, pure sine wave

Voltage regulation

120V + 12% (Line mode), 120V ±5% (Backup mode)

Frequency regulation

57-63Hz (Line mode), 60Hz ±0.3 Hz (Backup mode)

Total harmonic distortion

Less than 5% at full linear load (PF = 0.7)

Overload capacity

100% of 110% Load with 3-minute Delay

110% of 200% Load with 1-minute Delay

200% of full Load with less than 0.5- second delay

Transfer time

< 14mSec typical

Generator compatibility

Inverter Synchronization

Input
Current (max amp) 120/230 VAC

12 / 5

18 / 8

20 / 10

30 / 16

Power factor

> .95

Frequency

50/60 Hz (auto) / 45/65 Hz (inverter phase lock range)

Phase

Single-phase with ground

Voltage  

100-130VAC ± 4V

Voltage boost

10-12% (Low line boosted by 10-12%)

Frequency

57-63 Hz (60 Hz ± 5% or ± 3 Hz)

General
UPQ power conditioning topology

5 Stages of Isolation & Conversion / High Frequency, True On-line Digital Sine wave

Voltage Regulation
Input voltage range:

100 - 130 VAC

Full load without using battery

North America 80 to 140 VAC International 165 to 270 VAC

Half load without using battery

North America 75 to 140 VAC International 160 to 270 VAC

Output voltage regulation

± 2%

Isolation
Common-mode noise rejection

Yes

Normal-mode noise rejection

Yes

Suppression
IEEE 587/ANSI 62.41 3KA/6KV surge let-through (NA)

170 V normal mode (L or N) / 230 V common mode (L+N to G)

IEEE 587/ANSI 62.41 3KA/6KV surge let-through (international)

340 V normal mode (L or N) / 450 V common mode (L+N to G)

Joules (energy absorption)

300 Joules

Peak surge current (amp)

80,000 Amps

Multi-stage protection

Yes

Normal & common mode certified

Yes

Conditioning

Yes

Output total harmonic distortion

Less than 3% under linear load, less than 5% under non-linear load

Output frequency regulation

50/60 Hz ± 0.1 Hz (except brownout line synchronization)

Input frequency range

45-65 Hz

High Frequency On-Line Inverter
Inverter driver frequency

50 KHz

Overload capacity

>110% continuous

Crest factor

3:1

Transfer time

Zero

Efficiency

AC to AC > 85%

UPQ to bypass/bypass to UPQ

Zero cross transfer, less than 4 mSec. (2 mSec. minimum)

Transfer Switch
Type

Relay

Transfer Time

Bypass to Inverter, Inverter to Bypass: Less than 14ms

Transfer Criteria

Line Abnormal

Power Connector
Output of 120 V units

Two (2) NEMA Connectors

Additional output

Two (2) Terminal blocks

NEMA with Branch Bank Protection

Yes

Audible Alarm
Battery discharge

Battery Level: Two (2) Beeps every 2-10 Seconds

 

Low Battery: Two (2) Beeps every One (1) Second

Overload  

Two (2) Beeps every Second

Fault

Continuous Beep

Physical
WxDxH

17 x 9 x 5.2 in

17 x 10 x 5.2 in

Weight in lbs/kg

55 / 25

66 / 30

Battery Charger
Microprocessor controller

Yes

Expansion

Yes

Extended pack option

Yes

Connect/disconnect

Yes

Front Panel Display
System status information

Yes

Inverter status

Yes

Bypass status

Yes

Load status

5 segment

Battery status

5 segment

Diagnostic status

Yes

Diagnostics
POST

Yes

Bypass  

Yes

Line to output sync

Yes

Battery status

Yes

Inverter error

Yes

AC input failure

Yes

Overload  

Yes

Monitoring
Remote shutdown

Yes

Remote diagnostics

Yes

Scheduled shutdown

Yes

Input voltage  

Yes

Input frequency  

Yes

Output voltage  

Yes

Output frequency  

Yes

Output load

Yes

Reporting

Yes

Graphing

Yes

Plotting

Yes

Auto Restart (Input Voltage)
110/120 VAC

> 90 - 120 VAC

220 VAC

>100 - 200 VAC

DC Startup

Yes

Environment
Audible noise

< 50 dBA at 1 meter

Temperature 

-40 to 74 degrees C

Relative humidity 

0 to 95% non-condensing

Approvals
EMI

FCC Class A

Warranty
Length

1 year

Protection
Overload

> 100% full load / 15-20 sec delay

Short circuit

Yes

Over temperature

Yes

Bypass Box (Optional)
Dimensions WxDxH

4.7 x 4.6 x 4.6 in, 120.6 x 116.8 x 165mm

Transfer time

150 mSec

Weight in lbs/kg

< 7.7 lbs (3.5kg)

Interface Signal
RS-232 Interface

Yes

Connector

DB-9

External Self Test

Yes

External Battery
Full load run time

> 9 min

> 5 min

> 6 min

> 5 min

DC voltage

36

36

72

96

Recharge time

80% < eight (8) hours, full charge < 24 hours* 

Recharge current (AMPS)

1.5 AMPS

Temperature 

20° to 40° C (adjustable with use of heating pads)

Number of batteries (Typical)

3

3

6

8

*Additional battery modules / Ah batteries require additional time

 