| Output |
|
| Capacity (VA) |
1000 |
| Capacity (Watts) |
700 |
| Current (peak amp) 120/230 VAC |
9.1 / 4.3 |
| Waveform |
High resolution, pure sine wave |
| Outlets |
6 |
| Input |
|
| Current (max amp) 120/230 VAC |
12 / 5 |
| Power factor |
> .95 |
| frequency |
50/60 Hz (auto) / 45-65 Hz (inverter phase lock range) |
| General |
|
| UPQ power conditioning topology |
Dual stage isolation / high frequency, true on-line digital sine wave |
| Desktop configuration |
Yes |
| Rack mount configuration |
Yes |
| Voltage Regulation |
|
| Input voltage range: |
|
| Full load without using battery |
North America 80 to 140 VAC International 165 to 270 VAC |
| Half load without using battery |
North America 75 to 140 VAC International 160 to 270 VAC |
| Ouput voltage regulation |
±2% |
| Isolation |
|
| Common-mode noise rejection |
Yes |
| Normal-mode noise rejection |
Yes |
| Suppression |
|
| IEEE 587/ANSI 62.41 3KA/6KV |
170V normal mode (L or N) / 230V common mode (L+N to G) |
| surge let-through (NA) |
|
| IEEE 587/ANSI 62.41 3KA/6KA |
340V normal mode (L or N) / 450V common mode (L+N to G) |
| surge let-through (international) |
|
| Joules (energy absorption) |
300 |
| Peak surge current (amp) |
80,000 Amps |
| Multi-stage protection |
Yes |
| Normal & common mode certified |
Yes |
| Conditioning |
Yes |
| Output total harmonic distortion |
Less than 3% under linear load, less than 5% under non-linear load |
| Output frequency regulation |
50/60 Hz ±0.1 Hz (auto selected by microprocessor) |
| Input frequency range |
45-65 Hz for inverter phase lock frequency range |
| High Frequency On-Line inverter |
|
| Inverter driver frequency |
50 KHz |
| Overload capacity |
>110% continuous |
| Crest factor |
3:1 |
| Transfer time |
Zero |
| Efficiency |
85% |
| UPQ to bypass/bypass to UPQ |
Zero cross transfer, less than 4 mSec (2 mSec minimum) |
| Battery |
|
| Full load run time |
>5 min |
| Half load run time |
>15 min |
| DC voltage |
36 VDC |
| Recharge time |
5 to 8 hrs |
| Recharge current (amps) |
1.5 |
| Hot-swappable |
Yes |
| Front panel removal |
Yes |
| Modular Battery Packs |
Yes |
| Physical |
|
| WxDxH |
19 x 17.5 x 3.5 in (48 x 44.5 x 9 cm) |
| Weight in Ibs/kg |
40 |
| Battery pack weight in lbs/kg |
35 (optional) |
| Battery Charger |
|
| Microprocessor controller |
Yes |
| Expansion |
Yes |
| Extended pack option |
Yes |
| Connect/disconnect |
Yes |
| Front Panel Display |
|
| System status information |
Yes |
| Inverter status |
Yes |
| Bypass status |
Yes |
| Load status |
4 segment |
| Battery status |
4 segment |
| Diagnostic status |
Yes |
| Diagnostics |
|
| POST |
Yes |
| Bypass |
Yes |
| Line to output sync |
Yes |
| Battery status |
Yes |
| Inverter error |
Yes |
| AC input failure |
Yes |
| Overload |
Yes |
| Monitoring |
|
| Remote shutdown |
Yes |
| Remote diagnostics |
Yes |
| Scheduled shutdown |
Yes |
| Input voltage |
Yes |
| Input frequency |
Yes |
| Output voltage |
Yes |
| Output frequency |
Yes |
| Output load |
Yes |
| Reporting |
Yes |
| Graphing |
Yes |
| Plotting |
Yes |
| Auto Restart (Input Voltage |
|
| 120 VAC |
90-130 VAC |
| 230 VAC |
80-260 VAC |
| DC Start-up |
Yes |
| Environment |
|
| Audible noise |
< 50 dBA at 1 meter |
| Temperature (MIL-STD-810) |
-22° to 140° F (-30° to 60° C) |
| Relative humidity (MIL-STD-810) |
0 to 95% non-condensing |
| Vibration (MIL-STD-167) |
4-50 Hz / 2 g |
| Shock (MIL-STD-810E) |
2 g to 30 g |
| Approvals |
|
| CE and CE medical |
Yes |
| Warranty |
1 year parts and labor |
| Protection |
|
| Overload |
> 110% full load / 15-20 sec delay |
| Over/under voltage at I/P, O/P |
Inverter shutdown protection |
| Short circuit |
Yes |
| Over temperature |
Yes |